VAR95: Var Transducer

- Voltage Input 110 VAC, 220 VAC, 380 VAC

- Current Input 1 A, 5 A

- Analog Output 4-20 mA, 0-5 VDC

 

            The Var Transducers VAR95  are used to convert single or three phase unbalance load reactive power into a proportional load independent DC. output. Based fully electronic Time-Division Multiplication measuring principle, the reactive power of a network with any power factor range are linearly produced by Var Transducers output.

Calibration var of rated output

Connection V=110V V=220V V=380V
 
I=1A I=5A
I=1A I=5A
I=1A I=5A
Single Phase
±100var ±500var
±200var ±1000var
- -
3phase,3wire
±200var ±1000var
±400var ±2000var
±600var ±3000var
3phase,4wire
±200var ±1000var
±400var ±2000var
±600var ±3000var

Note. V= Line voltage

Equation to calculated measuring range

Measuring range = Calibration var x PT ratio x CT ratio

Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration var = 1000W

Measuring range = 1000 x (220/110) x (250/5) = 100 Kvar.

Specifications

Input

Number of Channel:

3 Channels

Input Type:

Current, Voltage (1 phase,3 phase 3 wire, 3 phase 4 wire)

Input Range:

Current (1, 5 A AC)

Voltage (110, 220, 380 VAC (Line voltage for 3 phase)

Power consumption:

< 0.2 VA for input current, < 0.4 VA for voltage input

Frequency:

50 Hz.

Analog Input

Number of Channel:

1 Channel

Output Type:

Current, Voltage

Output Range:

Current Max (-)1 to 1 mA (Load Resistance 10 KΩ)

Current Max 4 to 20 mA (Load Resistance 600 Ω)

Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω)

Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω)

Voltage Min 0 to 1 VDC (Load Resistance 500 Ω)

Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ)

Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ)

Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ)

Linearity:

< ¾ 0.5% of span

Power Requirements

Power Supply:

110, 220 VAC

Environmental Limits

Operating Temperature:

0 to 55 °C

Operating Humidity:

5 to 95 %RH

Storage Temperature:

0 to 70 °C

Physical Characteristics

Dimension:

W132 x H132 x D162 mm.

Mounting:

Wall Mount

Wiring:

Screw Terminals

Warranty

Warranty Period:

5 year

Ordering
Ordering Information: Specify connection, Input voltage, Input current, Output, Power supply
Example VAR95/3 phase 4 wire/380 VAC./5A/4-20 mA/220 VAC

 

Packagelist

Package Checklist

1. VAR95

Downloads