AL1000: Alarm Annunciator
แสดงตัวอย่างการต่อใช้งานร่วมกับ Lamp และ
Switch ภายนอก ไม่ใช่อุปกรณ์ของ AL1000
|
- 10 Channels Input
- Siren Relay Output - First Alarm Detect - Expandable Input Channel |
Alarm Annunciator AL1000 can control the alarm sequence of the alarm annunciator system. It can get 10 points of alarm signals and have output contact to control external alarm lamps for indicating the alarm status. If alarm is more than 10 points this module can be set to expand up to 32 units.
In many cases one alarm is caused by another and it is difficult to fine the first one, this is the reason why AL1000 should be installing. One alarm has been initiated LED will light up and the first alarm come with the quick flash and other will be slow flash. When alarm is come up Siren relay is “on” and it turn off by click “ACK” button while Alarm LED stops flashing, LED of alarm will turn off after problem have been fix and click “RESET”
Input Status | First Alarm | Subsequent Alarm | Siren |
First Alarm | Quick Flash | OFF | ON |
Subsequent Alarm | Quick Flash | Slow Flash | ON |
ACK | Steady - ON | Steady - ON | OFF |
Return to Normal | Steady - ON | Steady - ON | OFF |
Reset | OFF | OFF | OFF |
Test | Slow Flash | Slow Flash | ON |
Module AL1000 | Dimension |
ส่ง Output ไปยัง Pilot Lamp PL2000 เพื่อแสดงการแจ้งเตือน