DL2100: Data Logger

- 8 Analog Input Channels

- 4 Digital Input Channels

- 4 Digital Output Channels

- Memory 2MB

- RS232, RS485 (Isolated)

            Data Logger DL2100 can recode analog and digital signal by using its internal memory. The analog input are programmable It can be programmed for many types of sensor for example Thermocouple, PT100, Voltage, current.

            DL2100 is supplied with software for download data from DL2100 to computer. The data can be exported to program Excel, MS Words.


Connection via Ethernet (RC33)


Connection via Internet (RC34)

Specifications

Serial Interface

Serial Standards:

RS232 Connector RJ12 Connector

RS485 (Isolated) 2 Pin Terminal Block

Loading:

RS485 Max 32 Unit

Distance:

RS232 Length 15 m.

RS485 Length 1 Km.

Protocol:

MODBUS ASCII/RTU, Wisco ASCII

Supply Software:

Citect, Wonderware, LAB View etc.

Serial Parameter

Baud Rate:

4800, 9600, 19200, 57600

Data Bits:

8

Stop Bits:

1

Parity:

None

Analog Input

Number of Channel:

8 Channels

Input Type:

Programmable Input

Input Range:

Thermocouple (R, S, K, E, J, T, B)

RTD (PT100)

Voltage mVDC (0 to 100 mVDC)

Voltage (0 to 10, 0 to 5 VDC)

Current (0 to 20, 0 to 40 mA)

ADC Resolution:

16 Bits

Isolation:

Relay Isolated

Digital Input

Number of Channel:

4 Channels

Sensor Type:

wet Contact

wet Contact (DI to GND):

OFF : 0 to 3 VDC

ON : 12 to 24 VDC

Counter of Channel:

1 Channel (Channel 4 can use as counter)

Counter Frequency:

100 Hz

Digital Output

Number of Channel:

4 Channels

Output Type:

NPN Open Collector (Remote control)

Recording

Storage Internal:

2 Mbytes

Recording Interval:

1 Sec - 18 Hours (Programmable)

Record Mode:

Stop when full or Roll over

Record Mode:

Buttom SW, Set Time, Digital Trig

Data Format:

Can be Exported to MS Excel

Data Capacity:

80,580 Records (Enable AI 8 Ch/DI 4 Ch/DO 4 Ch/Time Stamp)

Power Requirements

Power Supply:

85 to 230 VAC

12, 24 VDC (Optional)

Power Consumption

Standby:

280 mA @ 12 VDC

Start Record:

350 mA @ 12 VDC

Environmental Limits

Operating Temperature:

0 to 55 °C

Operating Humidity:

5 to 95 %RH

Storage Temperature:

0 to 70 °C

Physical Characteristics

Dimension:

W160 x H90 x D60 mm.

Mounting:

DIN Rail

Warranty

Warranty Period:

5 year

Ordering
Ordering Information: Specify Power Supply, Memory
Example DL2100/220 VAC/2 Mbytes
Packagelist

Package Checklist

1. DL2100

2. RS-232 Cable

3. Resistor 250 Ω

4. Manual

5. CD Software

Downloads