CL24A: Data Logger

- 1 Channel Analog Input (4-20 mA,

  0-10 VDC)

- 2 Channels Totalizer

- Memory 256 KByte

- Data exportable to MS Excel

             Data Logger CL24A This device records small-scale measurement data-specifically analog signals and counter (totalizer) values-continuously within its internal memory, with each entry timestamped. Configurable analog input ranges include 4 - 20 mA, 1 - 5 VDC, 0 - 5 VDC, and 0 - 10 VDC, while the totalizer counts incoming pulses and stores the accumulated totals in memory.

             Data recorded in the CL24A can be retrieved by connecting a computer to the unit via an RS232 port or a modem, using dedicated software to transfer the data. The retrieved data can be displayed on the computer in either numerical or graphical formats. Furthermore, the data is compatible with other Windows-based applications-such as MS Excel-facilitating further calculations and report generation.

Connection to a computer via the Wireless (RC35).

Connection to a computer via the Ethernet (MC330).

Connection to a computer via the Internet (MC331).

Specifications

Serial Interface

Serial Standards:

RS232 Connector RJ12

Distance:

RS232 Length 15 m.

Serial Parameter

Baud Rate:

19200

Data Bits:

8

Stop Bits:

1

Parity:

None

Analog Input

Number of Channel:

1 Channel

Input Type:

Current, Voltage

Input Range:

Current (4 to 20 mA)

Voltage (0 to 5, 1 to 5, 0 to 10 VDC Optional)

ADC Resolution:

10 Bits

Accuracy:

± 0.2 % of span

Totalizer Input

Number of Channel:

2 Channels

Sensor Type:

NPN open collector or Dry contact

I/O Mode:

Even Counter

Dry Contact:

ON : Short to GND

OFF : Open

Counter Frequency:

maximum frequency 20 Hz

Minimum Pulse Width:

50 msec

Recording

Storage Internal:

256 Kbytes

Recording Interval:

1 Sec to 18 Hours (Programmable)

Record Mode:

Stop When Full or Roll Over

Recording by:

Magnetic Starter, DI Trig

Data Format:

Can be Exported to MS Excel

Data Capacity:

131,040 Records (3 Channels)

Power Requirements

Power Supply:

Lithium Battery 7.2 VDC@2.4 AH

(2 Year Life Time @ 15 Min. Interval Time)

Power Consumption

Standby:

30 µA @ 7 VDC

Start Record:

500 µA @ 7 VDC

Environmental Limits

Operating Temperature:

0 to 55 °C

Operating Humidity:

5 to 95 %RH

Storage Temperature:

0 to 70 °C

Physical Characteristics

Dimension:

W95 x H65 x D55 mm.

Protection:

IP65

Warranty

Warranty Period:

5 year

Ordering
Ordering Information: Specify Input Rang
Example CL24A/256Kbytes/4-20mA
Packagelist

Package Checklist

1. CL24A

2. RS-232 Cable

3.Input Cable

Downloads